Table 1 summarises the various substances used in the production plant of the biopharmaceutical manufacturer ChemBioEnv Inc. The corresponding auto ignition temperature for each substance is also listed in Table 1. Table 1 table 2 Substabce Auto ignition Temperature temperatue Class Acetic acid 485⁰C T1 450⁰C acetone 535⁰C T2 300⁰C Benzene 560⁰C T3 200⁰C Diethylether 170⁰C T4 135⁰C Ethanol 425⁰C T5 100⁰C T6 85⁰C ChemBioEnv Inc. has decided to buy a new pump for use in its production plant. The pump being considered has the following ATEX marking displayed on it: CE [ε x ⟩ II 2 G Ex d IIC T1 Basing your assessment on the ATEX Temperature Class data provided in Table 2, (a) which substances would this pump not be compatible with? (b) what temperature class would be suitable for all substances used in the production plant?